Operating Temperature | -40℃~+75℃,derating shall be applied when the temperature is above +55℃. |
Relative Humidity | ≤95%RH,condensation-free |
Cooling Method | Intelligent air cooling |
Altitude | 2000m,derating should be considered when the altitude is above 2000 meters. |
Rated Power | 150kW |
Voltage Range | 300Vdc~870Vdc(535Vdc~870Vdc full power output) |
Current Range | 0~280A |
Accuracy of Current Stabilization | ≤±1% |
Efficiency (Full Load) | > 99.5% |
Rated Power | 150kW |
Voltage Range | 650Vdc~900Vdc |
Current Range | 0~230A |
Current-sharing | Unbalance Degree<±5% |
Accuracy of Voltage Stabilization | <±0.5% |
Accuracy of Current Stabilization | ≤±1% |
Efficiency (Full Load) | >99.5% |
Dimension | 154mm(H)×385mm(W)×600mm(D) |
Weight | ≤30kg |
Connect Method | CAN |
MTBF | >500,000h |
Satisfied Standards | TUV CE/UL |